Kogeneracja, zasilacze UPS, falowniki, soft-starty

UPS Sentryum 10kVA-40kVA

Riello Sentryum 3 phase/3 phase UPS in the 10kW-40kW power range is a transformerless UPS that operates with double conversion technology, with PF=1. It has been designed in three versions, thus responding to the requirements of today's ever-changing technological thinking, environmental protection needs and demanding loads.

Main features

  • High efficiency, up to 99% in Smart Active mode
  • Low input current distortion THDI≤3
  • Input power factor 0.99
  • Mains power factor filtering and correction
  • Delayed start-up function
  • Power walk-in function for slow inverter start-up

Characteristics

The purpose of a UPS is to provide the ideal supply voltage for the equipment connected to it, whether mains power is present or not. Once connected and powered up, the UPS produces a sinusoidally alternating voltage of stable amplitude and frequency, regardless of any variations and/or fluctuations occurring on the mains. While the UPS is receiving power from the mains, the DSP processor ensures that the connected batteries remain charged. The DSP also monitors the amplitude and frequency of the mains voltage, the amplitude and frequency of the voltage generated by the inverter, the applied load, the internal temperature and the status of the connected batteries.

Three versions of Sentryum UPS

Riello presents the Sentryum UPS in three versions: Compact, Active, Xtend. The introduction of three versions of the unit allows the UPS to be even more closely matched to the needs of a specific working environment. The Compact UPS, thanks to its compact design, is able to operate in a very small space. Its footprint is only 0.2 m². The Active version allows a wide range of power requirements and back-up times, as well as one or two levels of battery charging. The Xtend has the largest capacity and back-up time options, with a compact design, the possibility to change the degree of protection of the housing and the integration of an isolation transformer.

In Riello Sentryum three-phase UPS, the most important aspects are efficiency, reliability, flexibility and compactness.

Efficiency levels in the Sentryum UPS

The Sentryum UPS reaches an efficiency level of 96.6% in on-line mode and 99% in Smart Active mode. It should be added that this high efficiency is achieved while reducing the footprint and components, as the UPS is made up of modules which reduce the space between components. The high efficiency is achieved through the use of three-level inverter circuits and resonant control.

High power in Sentryum 3-phase UPS

The use of digital control allows up to 270% of the inverter current to be transferred for 200 ms and 150% for 300 ms.

Modes of operation

  • On-line
  • Eco
  • Smart Active
  • Standby of

Smart battery management

The Sentryum UPS has a number of features that optimise battery operation, extending battery performance and life and making it reliable in emergency situations.

  • charge voltage compensation
  • automatic battery condition testing
  • deep discharge protection
  • wide operating voltage range of the charger

3 battery charging methods: single-level for VRLA AGM, two-level and cyclical

Communication

The UPS is equipped with a 5'' colour touchscreen display, which, among other things, enables the following to be carried out:

  • display of system status
  • switching the system on/off, activating the battery test and executing bypass commands
  • configuring the system, access levels and network services.

The home page displays a synoptic diagram of the general operating status of the system. The icons can be used to interact with the system and access further information. The display allows communication to be selected in Polish. From the display, the operating mode is selected, voltage and frequency are set, batteries are configured and an automatic battery test is programmed.

Remote control panel

The remote panel allows the UPS to be monitored remotely and provides a detailed real-time summary of the unit's status. The unit provides the operator with the ability to monitor the electrical values of the mains supply, outputs, batteries etc. and locate any alarm conditions.

Parallel work card

All Sentryum UPS can be connected in parallel with other units of the same size using an optional parallel operation card, which must be inserted into the slot provided for this purpose. A maximum of 8 three-phase units can be connected.

Optional extension cards

The UPS is equipped with two extension slots for additional communication or input/output extension cards, which enable the unit to communicate using the main communication standards, such as:

  • Second RS232 port
  • Serial duplicator
  • Ethernet network agent with TCP-IP, HTTP and SNMP protocol
    RS232 + RS485 port with JBUS/MODBUS protocol
  • Additional digital inputs
  • Additional voltage-free output contacts

Internal isolation transformer and supercapacitors optional for Xtend

The Sentryum Xtend UPS can be ordered in an optional OT version, where it will have a built-in isolation transformer connected to the output terminals of the Xtend UPS instead of internal batteries, and it can also be optionally equipped with supercapacitors instead of conventional batteries as a back-up power supply.

Other additional options in the Xtend UPS

Dust filter without power reduction for industrial environments

A special door for on-site installation is available for the XTEND - XTD series UPS as a kit with special dust filtration. This kit is designed for UPS located in dusty environments. The addition of the filter, when properly maintained, does not reduce the performance of the UPS (no loss of power).

IP 30 version for increased UPS protection

This option, available on request prior to the purchase of the UPS, provides a degree of protection up to IP30.

Version with optional roof

In this version, the UPS is equipped with a roof to protect it from vertically falling water droplets.

 

Specification

UPS S3T CPT-ACT-XTD 10

UPS S3T CPT-ACT-XTD 15

UPS S3T CPT-ACT-XTD 20

UPS S3T CPT-ACT-XTD 30

UPS S3T CPT-ACT-XTD 40

UPS model i moc

Model:
UPS S3T CPT-ACT-XTD 10
Active power [W]:
10000
Nominal power [VA]:
10000

Input

Voltage:
380/400/415 V 3-phase +N
Voltage tolerance:
400 V +/-20%
Frequency [Hz]:
50/70
Frequency tolerance:
40-72 Hz
Power factor:
0,99
Voltage distortion:
≤3%

By-pass

Voltage [V]:
3x380/400/415 3Ph+N
Phase voltage tolerance:
180-264 (selectable)
Frequency:
50/60 Hz (selectable)
Frequency tolerance:
+/-5% (selectable)

Output

Power factor:
1
Voltage:
3x380/400/415 V 3Ph+N selectable
Voltage stability:
+/- 1%
Dynamic stability:
EN 62040-3 class 1 - non-linear load
Total harmonic distortion THDv:
<1% resistive linear load ≤1.5% onon-linear load
Crest factor:
3:1
Frequency [Hz]:
50/60 selectable
Frequency stability on battery mode:
0.01%
Transfer time [ms]:
0

Others

Communications:
UPS status led bar - Graphic touch screen display - 2 slots for communications interface USB - RS232 - Contact interface with 5x opto insulated Input and 4x Output relays
Standards:
European directives: LV 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC EN 62040-3 VFI - SS - 111
Protection degree:
IP 20
Operating temperature [ºC]:
0-40
Relative humidity:
5-95% non-condensing
Dimensions ACT (WxDxH) [mm]:
380x850x1025
Dimensions XTD (WxDxH) [mm]:
440x840x1320
Weight without battery [Kg]:
48-72-103

UPS model i moc

Model:
UPS S3T CPT-ACT-XTD 15
Active power [W]:
15000
Nominal power [VA]:
15000

Input

Voltage:
380/400/415 V 3-phase +N
Voltage tolerance:
400 V +/-20%
Frequency [Hz]:
50/70
Frequency tolerance:
40-72 Hz
Power factor:
0,99
Voltage distortion:
≤3%

By-pass

Voltage [V]:
3x380/400/415 3Ph+N
Phase voltage tolerance:
180-264 (selectable)
Frequency:
50/60 Hz (selectable)
Frequency tolerance:
+/-5% (selectable)

Output

Power factor:
1
Voltage:
3x380/400/415 V 3Ph+N selectable
Voltage stability:
+/- 1%
Dynamic stability:
EN 62040-3 class 1 - non-linear load
Total harmonic distortion THDv:
<1% resistive linear load ≤1.5% non-linear load
Crest factor:
3:1
Frequency [Hz]:
50/60 selectable
Frequency stability on battery mode:
0.01%
Transfer time [ms]:
0

Others

Communications:
UPS status led bar - Graphic touch screen display - 2 slots for communications interface USB - RS232 - Contact interface with 5x opto insulated Input and 4x Output relays
Standards:
European directives: LV 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC EN 62040-3 VFI - SS - 111
Protection degree:
IP 20
Operating temperature [ºC]:
0-40
Relative humidity:
5-95% non-condensing
Dimensions ACT (WxDxH) [mm]:
380x850x1025
Dimensions XTD (WxDxH) [mm]:
440x840x1320
Weight without battery [Kg]:
50-74-105

UPS model i moc

Model:
UPS S3T CPT-ACT-XTD 20
Active power [W]:
20000
Nominal power [VA]:
20000

Input

Voltage:
380/400/415 V 3-phase +N
Voltage tolerance:
400 V +/-20%
Frequency [Hz]:
50/70
Frequency tolerance:
40-72 Hz
Power factor:
0,99
Voltage distortion:
≤3%

By-pass

Voltage [V]:
3x380/400/415
Phase voltage tolerance:
180-264 (selectable)
Frequency:
50/60 Hz (selectable)
Frequency tolerance:
+/-5% (selectable)

Output

Voltage:
3x380/400/415 V 3Ph+N selectable
Voltage stability:
+/- 1%
Dynamic stability:
EN 62040-3 class 1 - non-linear load
Total harmonic distortion THDv:
<1% resistive linear load ≤1.5% non-linear load
Crest factor:
3:1
Frequency [Hz]:
50/60 selectable
Frequency stability on battery mode:
0.01%
Transfer time [ms]:
0

Others

Communications:
UPS status led bar - Graphic touch screen display - 2 slots for communications interface USB - RS232 - Contact interface with 5x opto insulated Input and 4x Output relays
Standards:
European directives: LV 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC EN 62040-3 VFI - SS - 111
Protection degree:
IP 20
Operating temperature [ºC]:
0-40
Relative humidity:
5-95% non-condensing
Dimensions ACT (WxDxH) [mm]:
380x850x1025
Dimensions XTD (WxDxH) [mm]:
440x840x1320
Weight without battery [Kg]:
52-76-107

UPS model i moc

Model:
UPS S3T CPT-ACT-XTD 30
Active power [W]:
30000
Nominal power [VA]:
30000

Input

Voltage:
380/400/415 V 3-phase +N
Voltage tolerance:
400 V +/-20%
Frequency [Hz]:
50/70
Frequency tolerance:
40-72 Hz
Power factor:
0,99
Voltage distortion:
≤3%

By-pass

Voltage [V]:
3x380/400/415
Phase voltage tolerance:
180-264 (selectable)
Frequency:
50/60 Hz (selectable)
Frequency tolerance:
+/-5% (selectable)

Output

Voltage:
3x380/400/415 V 3Ph+N selectable
Voltage stability:
+/- 1%
Dynamic stability:
EN 62040-3 class 1 - non-linear load
Total harmonic distortion THDv:
<1% resistive linear load ≤1.5% non-linear load
Crest factor:
3:1
Frequency [Hz]:
50/60 selectable
Frequency stability on battery mode:
0.01%
Transfer time [ms]:
0

Others

Communications:
UPS status led bar - Graphic touch screen display - 2 slots for communications interface USB - RS232 - Contact interface with 5x opto insulated Input and 4x Output relays
Standards:
European directives: LV 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC EN 62040-3 VFI - SS - 111
Protection degree:
IP 20
Operating temperature [ºC]:
0-40
Relative humidity:
5-95% non-condensing
Dimensions ACT (WxDxH) [mm]:
380x850x1025
Dimensions XTD (WxDxH) [mm]:
440x840x1320
Weight without battery [Kg]:
N.A.-78-112

UPS model i moc

Model:
UPS S3T CPT-ACT-XTD 40
Active power [W]:
40000
Nominal power [VA]:
40000

Input

Voltage:
380/400/415 V 3-fazowe +N
Voltage tolerance:
400 V +/-20%
Frequency [Hz]:
50/70
Frequency tolerance:
40-72 Hz
Power factor:
0,99
Voltage distortion:
≤3%

By-pass

Voltage [V]:
3x380/400/415
Phase voltage tolerance:
180-264 (selectable)
Frequency:
50/60 Hz (selectable)
Frequency tolerance:
+/-5% (selectable)

Output

Voltage:
3x380/400/415 V 3Ph+N selectable
Voltage stability:
+/- 1%
Dynamic stability:
EN 62040-3 class 1 - non-linear load
Total harmonic distortion THDv:
<1% obciążenie rezystancyjne liniowe ≤1.5% obciążenie nieliniowe
Crest factor:
3:1
Frequency [Hz]:
50/60 selectable
Frequency stability on battery mode:
0.01%
Transfer time [ms]:
0

Others

Communications:
UPS status led bar - Graphic touch screen display - 2 slots for communications interface USB - RS232 - Contact interface with 5x opto insulated Input and 4x Output relays
Standards:
European directives: LV 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC EN 62040-3 VFI - SS - 111
Protection degree:
IP 20
Operating temperature [ºC]:
0-40
Relative humidity:
5-95% non-condensing
Dimensions ACT (WxDxH) [mm]:
380x850x1025
Dimensions XTD (WxDxH) [mm]:
440x840x1320
Net weight [Kg]:
Nie dot.-82-116

Cross-selling products

Karta NetMan 204 Plus

Karta NetMan 204 Plus

Karta NetMan 204 Plus pozwala na zarządzanie UPS-em bezpośrednio połączonym poprzez LAN 10/100 Mb z…

More 
Karta MultiCOM 302

Karta MultiCOM 302

MultiCom 302 pozwala na monitorowanie UPS-a za pomocą protokołu Modbus/JBUS poprzez łącze RS232 l…

More 
Karta MultiCOM 352

Karta MultiCOM 352

Karta MultiCOM 352 umożliwia przyłączenie dwóch urządzeń do jednego portu szeregowego zasilacza UPS…

More 
Karta MultiCOM 384

Karta MultiCOM 384

MultiCOM 384 zawiera zestaw styków przekaźnikowych do informowania o stanie i alarmach zasilacza UP…

More 
Karta MultiCOM 411

Karta MultiCOM 411

Karta MultiCOM 411 umożliwia podłączenie zasilacza UPS do sieci Profibus DP (Decentralised Peripher…

More 
Karta MultiCOM 421

Karta MultiCOM 421

MultiCOM 421 to karta komunikacyjna, która łączy zasilacz UPS z siecią PROFINET-IO. W środowiskach …

More 

Ask about the product

Do you prefer to contact us by phone?

Our offer

Accessibility settings
Line height
Letter spacing
No animations
Reading line
Speech
No images
Focus on content
Bigger cursor
Hotkeys