UPS CES GX 1kVA-10kVA

Karta katalogowa
The CES GX 1kVA -10 kVA UPS is a worthy successor to the CES UPS. The new generation of our 1-phase UPS offers excellent performance and a modern design. Designed in accordance with customers' needs, they guarantee the highest quality uninterruptible power supply for demanding applications, providing them with continuity of voltage and protection against unwanted phenomena occurring in the electrical network.

Main features

  • On-line UPS technology - double energy conversion
  • Wide input voltage range (110-300 VAC)
  • Output power factor of 0.8
  • Frequency 50/60 Hz
  • ECO mode - energy saving
  • EPO function
  • PFC - input power factor correction
  • LCD display
  • Cold start
  • Additional battery banks to extend operating autonomy
  • Division of output sockets into groups (1-3 kVA)
  • Interoperability with power generators

Characteristics

True online double conversion technology at CES GX

The CES GX true online UPS provides clean, high-quality power and fully protects connected equipment such as small computer centres, servers, telecommunications and industrial applications and medical devices.

Wide input voltage range

The high input voltage tolerance protects the battery packs from frequent discharge and extends their life considerably.

Programmable output sockets on CES GX UPS 1kVA - 3kVA

With the programmable output sockets, users can easily and independently control the load level of the UPS unit. When a power failure occurs, this function gives users the option of extending the back-up time when running on battery power, by switching off parts of the output sockets of lesser importance.

50/60Hz frequency converter in UPS CES GX

Users can set the output frequency to 50 Hz or 60 Hz, depending on their needs.

ECO operating mode and EPO function

ECO operating mode allows the UPS to achieve up to 99% efficiency, reducing energy consumption and running costs. Power is supplied to the loads via the UPS's internal by-pass and, when required, the UPS reverts to online double conversion mode. The EPO function is used to remotely shut down the UPS in the event of an emergency.

Communication diversity of the CES GX UPS: SNMP+USB+RS232

Advanced communication capabilities and available software allow the UPS to be monitored locally or remotely - via the network. CES GX UPS units are equipped with the following communication ports: USB, RS 232 and a slot for an SNMP network card.

Advanced battery management technology

The battery management of the CES GX uses a discontinuous battery charging system that, together with a temperature compensation function, not only significantly extends battery life, but also optimises charging times.

By-pass in CES GX 1kVA -10 kVA UPS

Each CES GX UPS has an automatic bypass and the 6kVA -10 kVA UPS models have a manual service by-pass to ensure continuity of power to loads during maintenance of the power supply.

Specification

UPS CES GX 1000

UPS CES GX 1500

UPS CES GX 2000

UPS CES GX 3000

UPS CES GX 6000

UPS CES GX 10000

UPS model i moc

Model:
UPS CES GX 1000
Active power [W]:
900
Nominal power [VA]:
1000

Input

Voltage:
230 V
Frequency [Hz]:
40-70
Power factor:
≥ 0.99
Input rated voltage [V]:
110/160-300 (for loads 100-80%/80-70%/70-60%/60-0%)

Output

Voltage:
200/208/220/230/240
Total harmonic distortion THDv:
≤2% THD linear load ≤4% THD non-linear load
Crest factor:
3:1
Voltage tolerance:
+/- 1%
Waveform:
Pure Sine Wave
Frequency [Hz]:
50/60
Frequency tolerance:
+/- 0.1
Transfer time [ms]:
0

Komunikacja

Standard configuration:
RS232/USB/EPO
Optional:
SNMP card or Modbus card

Others

Standards:
CE
Operating temperature [ºC]:
15-25
Dimensions (WxDxH) [mm]:
145x397x220
Net weight [Kg]:
12.5

UPS model i moc

Model:
UPS CES GX 1500
Active power [W]:
1350
Nominal power [VA]:
1500

Input

Voltage:
230 V
Frequency [Hz]:
40-70
Power factor:
≥ 0.99
Input rated voltage [V]:
110/160-300 (for loads 100-80%/80-70%/70-60%/60-0%)

Output

Voltage:
200/208/220/230/240
Total harmonic distortion THDv:
≤2% THD linear load ≤4% THD non-linear load
Crest factor:
3:1
Voltage tolerance:
+/- 1%
Waveform:
Pure Sine Wave
Frequency [Hz]:
50/60
Frequency tolerance:
+/- 0.1
Transfer time [ms]:
0

Komunikacja

Standard configuration:
RS232/USB/EPO
Optional:
SNMP card or Modbus card

Others

Standards:
CE
Operating temperature [ºC]:
15-25
Dimensions (WxDxH) [mm]:
145x397x220
Net weight [Kg]:
13.8

UPS model i moc

Model:
UPS CES GX 2000
Active power [W]:
1800
Nominal power [VA]:
2000

Input

Voltage:
230 V
Frequency [Hz]:
40-70
Power factor:
≥ 0.99
Input rated voltage [V]:
110/160-300 (for loads 100-80%/80-70%/70-60%/60-0%)

Output

Voltage:
200/208/220/230/240
Total harmonic distortion THDv:
≤2% THD linear load ≤4% THD non-linear load
Crest factor:
3:1
Voltage tolerance:
+/- 1%
Waveform:
Pure Sine Wave
Frequency [Hz]:
50/60
Frequency tolerance:
+/- 0.1
Transfer time [ms]:
0

Komunikacja

Standard configuration:
RS232/USB/EPO
Optional:
SNMP card or Modbus card

Others

Standards:
CE
Operating temperature [ºC]:
15-25
Dimensions (WxDxH) [mm]:
190x421x318
Net weight [Kg]:
25.8

UPS model i moc

Model:
UPS CES GX 3000
Active power [W]:
2700
Nominal power [VA]:
3000

Input

Voltage:
230 V
Frequency [Hz]:
40-70
Power factor:
≥ 0.99
Input rated voltage [V]:
110/160-300 (for loads 100-80%/80-70%/70-60%/60-0%)

Output

Voltage:
200/208/220/230/240
Total harmonic distortion THDv:
≤2% THD linear load ≤4% THD non-linear load
Crest factor:
3:1
Voltage tolerance:
+/- 1%
Waveform:
Pure Sine Wave
Frequency [Hz]:
50/60
Frequency tolerance:
+/- 0.1
Transfer time [ms]:
0

Komunikacja

Standard configuration:
RS232/USB/EPO
Optional:
SNMP card or Modbus card

Others

Standards:
CE
Operating temperature [ºC]:
15-25
Dimensions (WxDxH) [mm]:
190x421x318
Net weight [Kg]:
27

UPS model i moc

Model:
UPS CES GX 6000
Active power [W]:
6000
Nominal power [VA]:
6000

Input

Voltage:
230 V
Frequency [Hz]:
40-70
Power factor:
≥ 0.99
Input rated voltage [V]:
110/160-300 (for loads 100%/50%)

Output

Voltage:
200/208/220/230/240
Total harmonic distortion THDv:
≤3% THD linear load ≤6% THD non-linear load
Crest factor:
3:1
Voltage tolerance:
+/- 1%
Waveform:
Pure Sine Wave
Frequency [Hz]:
50/60
Frequency tolerance:
+/- 0.1
Transfer time [ms]:
0

Komunikacja

Standard configuration:
RS232/USB/EPO
Optional:
SNMP card or Modbus card

Others

Standards:
CE
Operating temperature [ºC]:
15-25
Dimensions (WxDxH) [mm]:
250x592x576
Net weight [Kg]:
81

UPS model i moc

Model:
UPS CES GX 10000
Active power [W]:
8000
Nominal power [VA]:
10000

Input

Voltage:
230 V
Frequency [Hz]:
40-70
Power factor:
≥ 0.99
Input rated voltage [V]:
110/160-300 (for loads 100%/50%)

Output

Voltage:
200/208/220/230/240
Total harmonic distortion THDv:
≤3% THD linear load ≤6% THD non-linear load
Crest factor:
3:1
Voltage tolerance:
+/- 1%
Waveform:
Pure Sine Wave
Frequency [Hz]:
50/60
Frequency tolerance:
+/- 0.1
Transfer time [ms]:
0

Komunikacja

Standard configuration:
RS232/USB/EPO
Optional:
SNMP card or Modbus card

Others

Standards:
CE
Operating temperature [ºC]:
15-25
Dimensions (WxDxH) [mm]:
250x592x576
Net weight [Kg]:
83

Cross-selling products

Karta SNMP

Karta SNMP

Karta komunikacyjna SNMP pozwala na czytelne przedstawienie informacji o stanie karty sieciowej ora…

More 
Karta AS 400

Karta AS 400

Karta ta umożliwia odwzorowanie stanu pracy UPS-a przy pomocy styków bezpotencjałowych (przekaźnikó…

More 

Ask about the product