Main features
- Overload resistance
- Galvanic isolation
- LCD screen
- High efficiency of up to 94.5% in ON LINE mode
Characteristics
An important feature of the Master HP UPS is its "zero impact" on the power source: the public grid or the generator with which it works. This is why the Master HP UPS is perfect for use in tandem with a generator set. The power supply has a very low input current distortion factor of < 3% and a high input power factor of 0.99.
In addition, the double conversion (VFI SS 111 class) with transformer arrangement at the inverter output, perfectly meets the critical requirements of high reliability imposed by today's consumers. An IGBT rectifier is used in place of the traditional thyristor rectifier.
Compact size
Master HP UPS has the advantage of being small in size while being powerful: 250 kVA has a footprint of 0.85 m². Thanks to access to the interior from the front of the UPS and the positioning of the fans on the upper level, the UPS is easy to install, even in small rooms.
UPS 100 kVA - 600 kVA - application flexibility
Master HP works well for a wide range of applications. This power supply is suitable for IT, server room power, medical device power, but it is also an industrial UPS. Master HP has a wide range of accessories and gives you the opportunity to get the most out of your UPS. It has the ability to parallelize up to 8 units in an n+1 system, and with the Hot System Expansion feature, adding a new UPS is possible when the other UPS are running.
Battery care system in Master UPS
An effective battery management and protection system ensures that the UPS's features are effectively utilised during an outage. Optimal battery life extension is ensured by:
- two-level charging system to reduce battery charging time
- temperature compensation and deep discharge protection to reduce battery ageing
- charge locking system
- a testing system to detect potential battery deterioration or damage.
Specification
UPS Master MHT 100
UPS Master MHT 120
UPS Master MHT 160
UPS Master MHT 200
UPS Master MHT 250
UPS Master MHT 300
UPS Master MHT 400
UPS Master MHT 500
UPS Master MHT 600
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
<1% linear load
<3% non-linear load
Frequency stability on battery mode:
110% dla 60 min; 125% dla 10 min; 150% dla 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
<1% linear load
<3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
< 1% linear load
< 3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
< 1% linear load
< 3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
< 1% linear load
< 3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
< 1% linear load
< 3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
< 1% linear load
< 3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
< 1% linear load
< 3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]:
UPS model i moc
Input
+/-2% (selectable from ±1% to ±5% from front panel)
By-pass
Output
3x380/400/415 V 3-phase+N (selectable)
Voltage static stability:
Total harmonic distortion THDv:
< 1% linear load
< 3% non-linear load
Frequency stability on battery mode:
110% for 60 min; 125% for 10 min; 150% for 1 min.
Others
up to 98% in SMART ACTIVE mode
VRLA AGM/GEL/NiCd/Li-ion/Flywheels/Supercaps
UPS status LEDs - Graphic display - 2 slots for communications interface - 2x RS23
European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility -- Directive and Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant -- Classification in accordance with IEC 62040-3 VFI - SS - 111
Operating temperature [ºC]: